Watts and amps are different quantities. The voltage is what joins them, it is different in every country, and on AC there is a power factor as well — so this asks rather than assumes.
Calculator
Try:
2000 W · 230 V · AC, single phase · PF 1
8.70 A
From I = P ÷ (V × PF). Change the supply and this number changes with it.
The same 2000 W, on every supply
Current drawn by an identical load in different countries
Supply
Voltage
Current
United Kingdom
230 V, 50 Hz
8.70 A
European Union
230 V, 50 Hz
8.70 A
India
230 V, 50 Hz
8.70 A
United States
120 V, 60 Hz
16.67 A
United States — 240 V circuit
240 V, 60 Hz
8.33 A
Canada
120 V, 60 Hz
16.67 A
Australia and New Zealand
230 V, 50 Hz
8.70 A
Japan
100 V, 50 Hz
20.00 A
A 100 V Japanese supply draws 2.3 times the current of a 230 V one for identical work, and a 120 V US supply 1.92 times. That is the reason a 3 kW kettle is ordinary in Britain and impossible on a standard American circuit: the current would be 25 A, and the outlet is rated for 15.
Watts, volt-amps and the gap between them
Real power2,000 Wwhat the meter bills
Apparent power2,000 VAwhat the cable carries
Reactive power0 VARnone — the load is resistive
A lower power factor means more current for the same work, not less — the current is divided by the power factor. At PF 1 this load draws 0% more current than a resistive load of the same wattage. Power factor is not efficiency: none of that extra current is wasted as heat in the load, but the cable, the breaker and the transformer all have to carry it, which is why a UPS is rated in VA and a heater in watts.
What a real power factor costs, at 230 V
Typical loads, with and without their power factor
Load
Power
PF
Current if resistive
Actual current
Electric kettle
2,000 W
1
8.70 A
8.70 A
Fan heater
2,000 W
0.99
8.70 A
8.78 A
Refrigerator
150 W
0.7
0.652 A
0.932 A
Air conditioner, 1.5 ton
1,500 W
0.85
6.52 A
7.67 A
Desktop PC, uncorrected supply
500 W
0.6
2.17 A
3.62 A
LED lighting circuit
100 W
0.9
0.435 A
0.483 A
Industrial motor, 7.5 kW
7,500 W
0.86
32.61 A
37.92 A
The power factors here are indicative of the class of equipment rather than measurements of any particular unit, and a modern appliance with active correction can be far better than the figure shown. The point is the direction: every motor-driven or switch-mode load draws more current than its wattage implies, and sizing a circuit from watts alone under-sizes it.
The rest of the relationships
Resistance, if purely resistive26.45 ΩR = V² ÷ P
If this were three phase instead5.02 A√3 = 1.7321 times less per line
Reading it backwards, 8.70 A gives2,000 Wthe same relation, rearranged
Three-phase distribution exists largely because of that third row. Splitting the same power across three conductors cuts the current in each by √3, and cable losses go as the square of current — so the same copper carries about three times the power. It is a wiring economy, not a property of the load.
What this converter covers
Single phase, three phase or DC, at UK, EU, India, US, Australian or Japanese nominal voltages — with the volt-amps shown beside the watts.
Watts to amps at any voltage, single phase, three phase or DC
Nominal supply voltages for the UK, EU, India, US, Canada, Australia and Japan
Watts against volt-amps and VAR, at any power factor
The √3 in three-phase power and between line-to-line and line-to-neutral
Resistance by Ohm’s law, and the relation read in reverse
Asks for the voltage UK, EU, India, US VA is not W Single and three phase
I = P ÷ (V × PF) single phase · I = P ÷ (√3 × V_LL × PF) three phase · VA = W ÷ PF
Scenario support
2000 W is 8.70 A at 230 V and 16.67 A at 120 V · 10 kW at 400 V three phase is 17.0 A per line
Watts do not convert to amps
“How many amps is 2000 watts?” is asked constantly and has no answer on its own. A watt is a rate of doing work. An amp is a rate of charge flowing. The thing that connects them is the voltage, and the voltage is not implied by either number.
The relation is P = V × I, so I = P ÷ V. Every calculator that hands back an answer without asking for a voltage has assumed one — usually the one common where its author lives. That assumption is invisible and it is wrong by nearly a factor of two for a large part of the world.
This tool asks. The region selector is there to make supplying the voltage one click rather than a lookup, and the box below it accepts anything if the installation is not at a nominal figure. But the voltage has to come from somewhere, and pretending otherwise is the failure this page exists to avoid.
The same is true in reverse, and for the third quantity. Amps to watts needs a voltage; watts to volts needs a current. Any two of the three determine the third, and no one of them determines anything.
Your country changes the answer
Mains voltage is roughly 230 V across Europe, the UK, India and Australia, and roughly 120 V across North America, with Japan lower still at 100 V. Current is inversely proportional to voltage, so identical work means a very different current.
A 2000 W appliance, on each nominal supply
Supply
Nominal voltage
Current
Against 230 V
Japan
100 V
20.00 A
2.30×
United States, Canada
120 V
16.67 A
1.92×
UK, EU, India, Australia
230 V
8.70 A
1.00×
US 240 V circuit
240 V
8.33 A
0.96×
This is the reason a 3 kW kettle is unremarkable in Britain and impossible on a standard American outlet. At 230 V it draws 13 A, which a UK ring circuit handles. At 120 V it would draw 25 A, and the outlet is rated for 15. American kettles are therefore about half the power, and take about twice as long — the physics is entirely in the voltage.
It is also why North American houses run large appliances on 240 V split-phase. An oven or a dryer or an EV charger needs the current to be manageable, and the only lever available is to double the voltage. India’s domestic supply is 230 V but three-phase is commonly quoted at 415 V rather than the European 400, which is the same system described with a slightly different nominal.
One caveat worth carrying: these are nominal figures. Both standards allow a tolerance band — a UK supply may legally sit between 216 and 253 V — so a real measurement will differ, and the current with it. For sizing, that tolerance usually matters less than the other margins a wiring code applies, but it is the reason a calculation and a clamp meter disagree.
Watts, volt-amps and power factor
On DC there is one kind of power. On AC there are three, and confusing them is the second-commonest error here after forgetting the voltage.
Real power in watts is work actually done. Apparent power in volt-amps is voltage times current, whatever the phase between them. Reactive power in VAR is the part that flows out and back without doing anything. Power factor is the ratio of the first to the second.
700 W of work, at three power factors, on a 230 V supply
Power factor
Apparent power
Current
Extra current
1.0 — a heater
700 VA
3.04 A
—
0.85 — a corrected motor
824 VA
3.58 A
+18%
0.70 — a fridge compressor
1000 VA
4.35 A
+43%
0.60 — an uncorrected PC supply
1167 VA
5.07 A
+67%
Note the direction, because it is the part people reverse: a worse power factor means more current for the same work. The current is divided by the power factor, not multiplied by it. A 0.7 power factor does not mean 30% of the energy is lost — it means 43% more current has to flow to deliver the same watts.
Power factor is not efficiency, and the distinction is practical rather than pedantic. The extra current is not consumed by the load; it goes out and comes back. But the cable, the breaker, the transformer and the generator all have to carry it, and cable losses go as the square of current. That is why a UPS is rated in VA rather than watts, why large industrial consumers are billed a penalty for poor power factor while domestic meters are not, and why generator sizing is a VA question.
One honest complication: the familiar power factor = cos φ holds only when both voltage and current are sinusoidal. Switch-mode supplies and LED drivers draw current in sharp pulses, and their true power factor is worse than their phase angle implies. The figures in the tool are indicative of a class of equipment rather than measurements, and a modern appliance with active correction can be far better than the number shown.
Three phase and the √3
Three-phase supplies carry a factor of √3 = 1.732, and it appears twice — in two different places, for two different reasons, which is why it is easy to apply once and forget the other.
First, between the two voltages. A three-phase supply has a line-to-neutral voltage and a line-to-line voltage, and the second is √3 times the first. A “400 V” European supply is 230.9 V per phase; a “415 V” Indian one is 239.6; a “208 V” American one is 120. Those pairs are the same system named at either end.
Second, in the power relation. For a balanced load, P = √3 × VLL× I × PF. Apply the single-phase formula to a three-phase load and the current comes out 1.732 times too high — a 10 kW load at 400 V and PF 0.85 draws 17.0 A per line, not 29.4.
Standard three-phase voltage pairs
Named as
Line-to-line
Line-to-neutral
Where
400/230
400 V
230.9 V
Europe, UK, Australia
415/240
415 V
239.6 V
India, older UK practice
208/120
208 V
120.1 V
North American commercial
200/100
200 V
115.5 V
Japan
Three-phase distribution exists largely because of the current reduction. The same power split across three conductors means √3 less current in each, and since cable losses go as the square of current, the same copper carries roughly three times the power. It is an economy of wiring rather than a property of the load — and it is also why motors above a few kilowatts are almost always three-phase.
Sizing a circuit from this
The number this page gives is the current a load draws at a stated voltage. That is the starting point of a cable calculation and nowhere near the end of one, and it is worth being explicit about the gap.
A wiring design has to account for how the cable is installed — clipped to a surface, buried in insulation, bunched with others — because each derates its capacity, sometimes by half. It has to account for ambient temperature, for the length of the run and the voltage drop along it, for the fault current the protective device must interrupt, and for whether the load starts gently or draws six times its running current for a second. Motor circuits, in particular, are sized on starting behaviour rather than steady-state current.
Then there is diversity. A consumer unit does not need to supply the sum of every circuit’s maximum at once, and every national code has its own method for deciding how much less. Adding up the currents from a page like this one gives a number that is real but not the number a designer uses.
What this is good for: checking whether an appliance is plausible on a circuit, understanding why an import behaves differently, sanity-checking a quotation, working out whether a generator or a UPS is big enough in VA, and seeing what a power factor is costing. For anything that will actually be installed, the calculation belongs to a qualified electrician working to the code that applies where you are — in most countries that is not merely advisable but a legal requirement.
Related calculators
Other electrical and power tools:
PowerWatts, kilowatts, horsepower and BTU per hour — with mechanical and metric horsepower listed apart, since they differ by 1.4% under one word.
Wire GaugeAWG and SWG to mm, mm² and circular mils, with resistance and voltage drop — and the 14–21% gap the equivalence charts hide.
EnergyJoules, kilojoules, calories, food Calories, kWh, BTU and therms — with the two calories listed apart, since one is a thousand of the other.
ForceNewtons, kgf, lbf, kip, poundals and dynes with exact factors — keeping mass in its own panel, and the three tons-force apart.
Frequency to WavelengthFrequency, wavelength, photon energy and wavenumber — in vacuum and in the medium, including coax velocity factors.
The nominal voltages here come from the two standards that set them — IEC 60038 for the harmonised 230/400 V system and ANSI C84.1 for the North American 120/240 V one — and they are nominal rather than measured: both standards define a tolerance band around the declared figure, which is why a UK socket can read anywhere from 216 to 253 V and still be compliant. The power definitions follow IEEE 1459, which is also the reason this page is careful to say that power factor equals cos φ only under sinusoidal conditions.
IEC 60038 — IEC standard voltagesInternational Electrotechnical Commission · verified 2026-09-07 · The harmonised 230 V single-phase and 400 V three-phase nominal values used across Europe, and the tolerance bands that make them nominal rather than measured figures
IEEE Std 1459 — Definitions for the Measurement of Electric Power QuantitiesInstitute of Electrical and Electronics Engineers · verified 2026-09-07 · The formal definitions of active, reactive and apparent power and of power factor — including that the simple cos φ form holds only for sinusoidal conditions, which is why a distorting load has a worse power factor than its phase angle suggests
Conversion note
This is unit arithmetic, not a wiring design, and the difference matters. Sizing a cable or a protective device involves far more than the current a load draws at nominal voltage: the installation method and grouping of cables, ambient temperature, the length of the run and the permitted voltage drop, the fault current the circuit must clear, the starting current of motor loads, harmonics on the neutral, and diversity across a distribution board all change the answer, and every national wiring code handles them differently. Nominal supply voltages are declared values with a tolerance band around them, so a real installation sits above or below the figure used here. Power factors shown are indicative of a class of equipment, not measurements of your unit, and for a distorting load the true power factor is worse than the phase angle alone suggests. Electrical work is regulated in most countries. Use these figures to reason and to check, and have anything that will be installed designed and certified by a qualified electrician working to the code that applies where you are.
Published the Watts to Amps Calculator: power, current and voltage related across DC, single-phase AC and three-phase AC, with apparent and reactive power alongside the real power.
Establishes that watts do not convert to amps at all -- they are different quantities joined by the voltage, so the tool requires a voltage and returns nothing without one rather than assuming a regional default.
Shows why the assumption matters: an identical 2000 watt appliance draws 8.70 amps on a 230 volt supply, 16.67 on a 120 volt one and 20.00 on Japan's 100 volt, so a silently assumed voltage is wrong by up to 2.3 times.
Carries nominal supply voltages for the UK, European Union, India, United States, Canada, Australia and Japan, and states that all of them are declared nominal values with a tolerance band rather than measurements.
Explains why a 3 kW kettle is ordinary in Britain and impossible on a standard American outlet, and why North American houses run ovens and EV chargers on 240 volt split-phase.
Separates real power in watts, apparent power in volt-amps and reactive power in VAR, and states the direction people reverse: a worse power factor means MORE current for the same work, because the current is divided by the power factor rather than multiplied by it.
Says plainly that power factor is not efficiency -- the extra current is not consumed by the load, but the cable, breaker and transformer all carry it, which is why a UPS is rated in volt-amps and a heater in watts.
Handles the two separate appearances of root three in three-phase supplies: between the line-to-line and line-to-neutral voltages, and in the power relation, where applying single-phase arithmetic overstates the current by 1.732.
Notes the standard voltage pairs 400/230, 415/240, 208/120 and 200/100 as the same system named at either end, and that three-phase distribution exists because splitting power across three conductors lets the same copper carry about three times the power.
Draws the line between unit arithmetic and a wiring design, naming what a real cable calculation adds -- installation method, grouping, ambient temperature, voltage drop, fault current, motor starting current, harmonics and diversity -- and that electrical work is regulated in most countries.
Verified by 50 automated cases, asserting that current refuses to compute without a positive voltage in every phase mode, that single-phase arithmetic overstates a three-phase current by exactly root three at every input, and that a poor power factor increases current rather than decreasing it.
Add this calculator to your site
Responsive embed — and private: nothing your visitors type leaves their browser.